Calculate Three-Phase Power Factor per Phase and Total
Calculate three-phase power factor (PF, cos φ) for each phase and in total from L1, L2 and L3 active power, voltage and current. For energy meters, power analyzers, motors, compressors and switchboards that report power but no power factor. Find the phase with poor power quality and watch the total against your utility’s reactive power penalty limit.
Who it’s for
Energy managers, facility engineers and electricians asking “what is the power factor on each phase?”, “is our cos φ low enough to pay a reactive power penalty?”, “which phase of the motor or switchboard has the poor power factor?” — when the meter reports active power, voltage and current for L1, L2 and L3 but no power factor.
What it does
Reads the latest powerL1, powerL2 and powerL3 (active power, W), voltageL1, voltageL2 and voltageL3 (V) and currentL1, currentL2 and currentL3 (A) telemetry. It writes the power factor of each phase as powerFactorL1, powerFactorL2 and powerFactorL3, and the power factor of the whole load as powerFactor:
When the phases are strongly unbalanced, engineers define the total power factor in more than one way. This field uses the arithmetic one shown above, because the readings of any meter allow it. A meter that computes its own total in another way can show a very different number. For example, with one phase at power factor 1 and two phases at 0.5, this field shows 0.80 and such a meter can show 0.92.
The voltage must be phase-to-neutral (for example 230 V), not phase-to-phase (400 V). With phase-to-phase voltage every result is too low.
A minus means power flows to the grid. Some meters use another convention, where the sign shows an inductive or capacitive load. When some phases consume and others export, for example on a site with solar panels, their active power cancels out in the total, so powerFactor can be close to 0 while every phase is fine. Watch the phase keys on such sites. Meters round their readings, so active power can be a little higher than voltage × current. The field then writes 1 or −1.
A phase with no current, or with a reading that is not a number such as ERR, gets no new value, so its key keeps the last value. The total then comes from the other phases, and when no phase carries current the field writes nothing.
If your meter already sends powerFactor for the whole load, rename the powerFactor output of this field, as described in How to customize. With the same key, the field writes over the meter’s own value.
How to customize
- To use this on your meter’s keys — change the Time series key on the nine arguments, from
powerL1tocurrentL3(e.g. powerL1 → activePowerA, voltageL1 → voltageA, currentL1 → currentA). - To rename the outputs — open the Script and replace the keys in the
valuesobject (e.g. powerFactor → totalPowerFactor). - To show 3 decimals — open the Script and change
100and100.0in thepffunction to1000and1000.0. - To timestamp the results with server time — open the Script and change the last line to return
valuesonly, withoutts. - To filter, transform, or forward the result to external systems — switch Strategy to Process via Rule Chains. Rule nodes then receive the values and can drop them, change them, save them conditionally, or push them to an external system.
See also
To raise an alarm when the power factor stays below the tariff limit:
Low Power Factor AlarmShare Your Calculated Field with the Community