Three-Phase Phase Loss Alarm
Raise a critical alarm the moment a phase is lost on a three-phase supply, with the lost phase in the alarm details. Catches phase failure, a blown fuse or a missing phase on motor, pump and compressor feeds, switchboards and energy meters. A separate warning shows a phase that the meter cannot read.
Who it’s for
Electricians, maintenance engineers and facility managers asking “has a phase dropped out on this motor feed?”, “did a fuse blow on the pump or compressor supply?”, “is the meter on this switchboard still reading all three phases?” — when a lost phase must reach someone at once, before a machine overheats on two phases or stops.
What it does
Reads the result of the phase loss calculated field: how many phases are lost, how many the meter cannot read, and their names. A lost phase raises a Critical alarm at once, with the lost phases in the alarm details (for example L2). A phase that the meter cannot read, such as one that reports OFF or ERR, raises a Warning alarm when it stays unreadable for 5 minutes. When a phase is lost while the Warning is active, the alarm goes up to Critical. The alarm clears when every phase is back and readable.
The Critical alarm has no waiting time on purpose: a motor that runs on two phases overheats within minutes. The Warning waits, because a meter can send one bad reading and then recover.
How to set up
The rule has default values for every setting, so it works as soon as it is installed. Install on a device profile so the alarm covers every meter of that type at once and automatically picks up any new meter added later. Single-device installs are also supported.
The rule reads lostPhaseCount, lostPhaseNames, unknownPhaseCount and unknownPhaseNames. Install this calculated field on the same devices first, so these keys exist:
How to customize
- To use keys from another source — change the Time series key on the
lostCount,lostNames,unknownCountandunknownNamesarguments. - To use a different hold-time attribute name — change the Attribute key on the
unknownHoldMinutesargument (e.g.phaseUnknownHoldMinutes→meterErrorMinutes). - To change how long a phase must stay unreadable before the Warning — change the Default value on the
unknownHoldMinutesargument. - To tune the hold time at runtime without editing the rule — set the value on the entity as a regular server-side attribute. It can be edited directly from a dashboard using Update Multiple Attributes input widget:
- Per device — set
phaseUnknownHoldMinuteson the meter itself. The per-device value overrides the Default value. - Per customer (in deployments that use customers) — change Entity type on the
unknownHoldMinutesargument to Current owner, then set the attribute on the customer. Every meter that customer owns picks up that value.
- Per device — set
- To make the alarm manual-clear-only — remove the Clear condition. The alarm then stays active until an operator clears it.
- To raise the alarm only during set hours each week — in the Schedule of both the Warning and Critical trigger conditions, choose Active at a specific time (or Custom for different hours per day). The schedule repeats every week. For different hours per site, add an argument that reads the schedule JSON from a server-side attribute on the device, and set its Default value to
{}so a device without the attribute raises the alarm at any time. Then switch the Schedule of both trigger conditions to Dynamic and pick that argument in Argument. - To control where the alarm shows up — toggle the propagation flags under Advanced settings.