Three-Phase Voltage Imbalance Alarm
Raise an alarm when the three-phase supply voltage stays unbalanced: a major alarm above 2 % and a critical alarm above 5 %, with the imbalance in the alarm details. Protects motors, pumps, compressors and switchboards from voltage unbalance, phase unbalance and uneven phase voltages that make them overheat. The limits follow NEMA MG 1 and can be set per device.
Who it’s for
Maintenance engineers, electricians and energy managers asking “is the supply voltage on this motor too unbalanced?”, “is one phase of the feeder lower than the others for too long?”, “is the voltage unbalance on this pump, compressor or switchboard above 2 %?” — when an unbalanced supply makes motors run hot and wear out long before anyone sees a fault.
What it does
Reads the voltage imbalance in percent that the voltage imbalance calculated field writes. When the imbalance stays above 2 % for 5 minutes, the rule raises a Major alarm. When it stays above 5 % for 1 minute, the rule raises a Critical alarm, or moves an active Major alarm up to Critical. The alarm details show the imbalance and the limit it passed. The alarm clears when the imbalance stays below 1.5 % for 5 minutes. A value between 1.5 % and 2 % keeps the alarm as it is, so a reading near the limit does not open and close the alarm again and again.
The default limits follow NEMA MG 1 for line-to-line voltages: a motor must run at a lower load when the unbalance grows above 1 %, and it should not run above 5 %. Phase-to-neutral voltages of the same supply give a higher number, often about twice as high, so set the limits for the kind of voltage the field reads.
The alarm opens or clears as soon as the waiting time ends, even if no new reading arrives. A reading that is not a number, such as ERR, does not raise or clear the alarm.
How to set up
The rule has default values for every threshold, so it works as soon as it is installed. Install on a device profile so the alarm covers every meter of that type at once and automatically picks up any new meter added later. Single-device installs are also supported.
The rule reads voltageImbalancePercent. Install this calculated field on the same devices first, so this key exists:
How to customize
- To use a key from another source — change the Time series key on the
metricargument (e.g.voltageImbalancePercent→ voltageUnbalance). - To use different threshold or hold-time attribute names — change the Attribute key on the threshold and hold-time arguments (e.g.
voltageImbalanceWarningPercent→ imbalanceLimit). - To change the thresholds used when no per-device attribute is set — change the Default value on the
warningThreshold,criticalThresholdandclearThresholdarguments. Keep the clear threshold below the warning threshold. When the field reads phase-to-neutral voltages, about twice the default values fit (e.g. 4, 10 and 3). - To change how long the imbalance must last before the alarm opens or clears — change the Default value on the
warningHoldMinutes,criticalHoldMinutesandclearHoldMinutesarguments. - To tune thresholds and hold times at runtime without editing the rule — set the value on the entity as a regular server-side attribute. It can be edited directly from a dashboard using Update Multiple Attributes input widget:
- Per device — set the attribute (e.g.
voltageImbalanceWarningPercent,voltageImbalanceWarningHoldMinutes) on the meter itself. The per-device value overrides the Default value. - Per customer (in deployments that use customers) — change Entity type on the relevant argument to Current owner, then set the attribute on the customer. Every meter that customer owns picks up that value.
- Per device — set the attribute (e.g.
- To make the alarm manual-clear-only — remove the Clear condition. The alarm then stays active until an operator clears it.
- To raise the alarm only during set hours each week — in the Schedule of both the Major and Critical trigger conditions, choose Active at a specific time (or Custom for different hours per day). The schedule repeats every week. For different hours per site, add an argument that reads the schedule JSON from a server-side attribute on the device, and set its Default value to
{}so a device without the attribute raises the alarm at any time. Then switch the Schedule of both trigger conditions to Dynamic and pick that argument in Argument. - To control where the alarm shows up — toggle the propagation flags under Advanced settings.