Calculate Three-Phase Voltage Imbalance Percentage
Calculate three-phase voltage unbalance in percent from L1, L2 and L3 phase voltages with the NEMA method: the largest deviation from the mean, divided by the mean. For motor protection, power quality checks, energy meters, power analyzers, pumps, compressors and switchboards. Writes one key for dashboards and unbalance alarms.
Who it’s for
Maintenance engineers, electricians and energy managers asking “how unbalanced is the supply voltage on this motor?”, “is one phase of the feeder lower than the others?”, “is the voltage unbalance above 1 % or 2 %?” — when the meter reports each phase voltage on its own and nobody sees the unbalance until a motor runs hot or trips.
What it does
Reads the latest voltageL1, voltageL2 and voltageL3 telemetry, finds the mean of the three, and writes the largest deviation of a phase from that mean as a percent of the mean, as voltageImbalancePercent:
This is the NEMA MG 1 definition of voltage unbalance. It uses only the voltage magnitudes, so any three-phase meter can feed it. The IEC method uses phase angles too and can give a slightly different number. NEMA MG 1 and the usual limits of 1 %, 2 % and 5 % are for line-to-line voltages. Phase-to-neutral voltages work too, but for the same supply they give a higher number, often about twice as high, so set your limits for the kind of voltage you feed it. Feed it three values of one kind: all line-to-line or all phase-to-neutral voltages.
Some examples with line-to-line voltages: 408, 400 and 392 V give 2.0 %, and 420, 400 and 380 V give 5.0 %. With phase-to-neutral voltages, 234.6, 230 and 225.4 V give 2.0 %, while the line-to-line voltages of the same supply give 1.0 %. A lost phase (0, 230 and 230 V phase-to-neutral) gives 100.0 %. One decimal lets you tell 1.9 % from 2.1 % near those limits.
The field works best when the meter sends the three voltages in one message. When they arrive one by one, the field computes after each of them with the last values of the other two. A supply loss then writes 100.0 % and 200.0 % first, and 200.0 % stays the latest value until the supply comes back.
How to customize
- To use this on your meter’s keys — change the Time series key on the
phaseL1,phaseL2andphaseL3arguments (e.g. voltageL1 → Ua). - To rename the output — open the Script and replace
voltageImbalancePercentin the returned object with your own key (e.g. voltageUnbalance). - To show two decimals — open the Script and change the
1intoFixed(…, 1)to2. - To timestamp the result with server time — open the Script and return
{ voltageImbalancePercent: … }at the top level instead of insidevalues. - To filter, transform, or forward the result to external systems — switch Strategy to Process via Rule Chains. Rule nodes then receive the value and can drop it, change it, save it conditionally, or push it to an external system.
See also
Unbalanced phase currents are the other half of the picture. To raise an alarm when the current of one phase moves away from the others:
Motor Phase Current Imbalance AlarmTo raise an alarm when the voltage unbalance stays above the limit: