Modbus Extension Configuration

This guide will help you to get familiar with Modbus extension configuration for ThingsBoard IoT Gateway. Use general configuration to enable this extension. We will describe extension configuration file below.

Extension configuration: modbus-config.json

Extension configuration is a JSON file that contains information about how to connect and monitor a list of Modbus slaves. The root JSON element should contain “servers” array. Each server (slave or gateway) in the array is configured using following properties:

Basic connection properties

Property Description
transport Protocol configuration
devices Devices (slaves) mapping configuration

For Example:

{
  "servers": [
    {
      "transport": {
      ...
      },
      "devices": [
      ...
      ]
    }
  ]
}
      

Transport properties

Modbus extension supports “tcp”, “udp” and “rtu” transports.

TCP transport
Property Description Default value
type Transport type tcp
host Host localhost
port Port 502
timeout Socket timeout in milliseconds 3000
reconnect Automatically reconnect true
rtuOverTcp Enable RTU over TCP feature false

Example of “tcp” transport configuration:

{
      ...
      "transport": {
        "type": "tcp",
        "host": "localhost",
        "port": 654,
        "timeout": 5000,
        "reconnect": true,
        "rtuOverTcp": false
      }
      ...
}
      
UDP transport
Property Description Default value
type Transport type udp
host Host localhost
port Port 502
timeout Socket timeout in milliseconds 3000

Example of “udp” transport configuration:

{
      ...
      "transport": {
        "type": "udp",
        "host": "localhost",
        "port": 502,
        "timeout": 5000
      }
      ...
}
      
RTU transport
Property Description Values
type Transport type rtu (default)
portName Name of port  
encoding Serial encoding ascii,rtu
baudRate Baud rate 9600,115200 …
dataBits Number of data bits 7,8
stopBits Number of stop bits 1,2
parity Type of parity none,even,odd
timeout Socket timeout in milliseconds 3000 (default)

Example of “rtu” transport configuration:

{
      ...
      "transport": {
        "type": "rtu",
        "portName": "COM1",
        "encoding": "ascii",
        "baudRate": 115200,
        "dataBits": 7,
        "stopBits": 1,
        "parity": "even",
        "timeout": 5000
      }
      ...
}
      

Device mapping

Device mapping configuration setup rules of Modbus slave(s) monitoring.

Property Description Values
unitId Modbus unit identifier 1-247
deviceName Arbitrary name of device  
attributesPollPeriod Period of polling attributes in milliseconds 1000 (default)
timeseriesPollPeriod Period of polling timeseries in milliseconds 1000 (default)
attributes Attributes (tags) mapping rules  
timeseries Timeseries (tags) mapping rules  

Example of device mapping configuration:

{
      ...
      "devices": [
        {
          "unitId": 1,
          "deviceName": "Temp Sensor",
          "attributesPollPeriod": 5000,
          "timeseriesPollPeriod": 5000,
          "attributes": [
            {
            ...tag mappings
            }
          ],
          "timeseries": [
            {
            ...tag mappings
            }
          ]
        }
      ]
      ...
}

Tag mapping

Tag mapping configuration setup rules of Modbus entities (coils, discrete inputs, holding and input registers) monitoring and conversion to ThingsBoard Key-Value format.

Property Description Values
tag Arbitrary name of Modbus entity what will be read  
pollPeriod Period of polling in milliseconds. Overrides values defined on device mapping level  
type Type of data to what Modbus entity will converted boolean,long,double,string
functionCode Modbus function code 1,2,3,4
address Address of coil/discrete input/register 0-65535
registerCount Number of hardware registers to be read 1 (default) -…
bit ONLY boolean: Index of bit to be read (ascending numbering from right to left) 0-15
byteOrder Order of bytes BIG (default),LITTLE,1023,CD AB EG FH
Modbus functions

The Modbus extension supports the following Modbus functions:

Data conversion rules

The hardware manufactures can implement various data types. Here are mapping rules that help to convert common hardware data types to Thingsboard key value format:

Hardware type Thingsboard type Function code Hardware registers Note
Bool boolean 1-4 1 Use bit property for function codes 3 and 4
Word long 3-4 1  
DWord/Integer long 3-4 2  
Integer64 long 3-4 4  
Float double 3-4 2  
Double double 3-4 4  
String string 3-4 1-… 1 register = 2 characters
Byte order

The byte order can be different among hardware manufactures. To correctly map data to Thingsboard types you must specify the byte order. There are several ways how to do it:

Hardware type Marker limits
Bool [0-1],[A-B] for function codes 3 and 4
Word [0-1],[A-B]
DWord/Integer [0-3],[A-D]
Integer64 [0-7],[A-H]
Float [0-3],[A-D]
Double [0-7],[A-H]
String [0-1],[A-B]
Examples

Read each second (1000 ms - default value for polling) a coil to get a boolean value.

  "timeseries": [
    {
      "tag": "Coil",
      "type": "boolean",
      "functionCode": 1,
      "address": 75
    }
  ]

Read each second (1000 ms - default value for polling) 14th bit of a holding register in little-endianness to get a boolean value.

  "timeseries": [
    {
      "tag": "BooleanValue",
      "type": "boolean",
      "functionCode": 3,
      "address": 150,
      "bit": 14,
      "byteOrder": "little"
    }
  ]

Read each second (1000 ms - default value for polling) 4 holding register in the ‘CD AB EF GH’ byte order to get a long value.

  "timeseries": [
    {
      "tag": "LongValue",
      "type": "long",
      "functionCode": 3,
      "address": 154,
      "registerCount": 4,
      "byteOrder": "CD AB EF GH"
    }
  ]

Read each hour (3600000 ms) 6 input registers in big-endianness to get a string 12-character long.

  "attributes": [
    {
      "tag": "Serial number",
      "type": "string",
      "functionCode": 4,
      "address": 146,
      "registerCount": 6,
      "pollPeriod": 3600000
    }
  ]

Server-side RPC

For general information how to use server-side RPC feature please visit this guide.

Multiple tags write

This RPC method allows user to simultaneously write values to the multiple tags of the connected device.

Request format
Property Description Value
method RPC method name write
params Format of RPC method parameters JSON array of objects
Method parameters format

The method parameters are represented as JSON array of objects. Each object describes how the value needs to be encoded and written via Modbus protocol. Each object has the following structure:

Property Description Value
tag Arbitrary name of Modbus tag that will be written  
value The value that will be written boolean,long,double,string
functionCode Modbus function code 5,6,16
address Address of coil/register 0-65535
registerCount Number of hardware registers to be written 1 (default) -…
byteOrder Order of bytes BIG (default),LITTLE,1023,CD AB EG FH

NOTE: For more details about the registerCount and byteOrder parameters see above the Tag mapping section.

The Modbus RPC extension supports the following Modbus functions:

Response format
Success
Property Description Value
tag name 1 Name of Modbus tag that has been written ok
tag name 2 Name of Modbus tag that has been written ok
ok
Global error
Property Description
error Description of the error
Tag error
Property Description
tag name 1 Description of the error while writing the tag value
tag name 2
Examples
Request
    [
        {
            "tag": "WriteCoil",
            "value": true,
            "functionCode": 5,
            "address": 1
        },
        {
            "tag": "WriteLittleWord",
            "value": 123,
            "functionCode": 6,
            "address": 1,
            "byteOrder": "LITTLE"
        },
        {
            "tag": "WriteBigWord",
            "value": 4567,
            "functionCode": 6,
            "address": 2,
            "byteOrder": "BIG"
        },
        {
            "tag": "WriteInteger1032",
            "value": 345678,
            "functionCode": 16,
            "address": 3,
            "byteOrder": "1032",
            "registerCount": 2
        },
        {
            "tag": "WriteLong10325476",
            "value": 9223372036854775806,
            "functionCode": 16,
            "address": 7,
            "registerCount": 4,
            "byteOrder": "1 0 3 2 5 4 7 6"
        },
        {
            "tag": "WriteFloat1032",
            "value": 3.4028234e+38,
            "functionCode": 16,
            "address": 11,
            "registerCount": 2,
            "byteOrder": "B A D C"
        },
        {
            "tag": "WriteDouble45670123",
            "value": 1.7976931348623156e+308,
            "functionCode": 16,
            "address": 13,
            "registerCount": 4,
            "byteOrder": "45670123"
        },
        {
            "tag": "WriteString",
            "value": "Salute!",
            "functionCode": 16,
            "address": 17,
            "registerCount": 5
        }
    ]
Response
    {
        "SuccesWriteTag": "ok",
        "ErrorWriteTag": "No tag found"
    }
    {
        "error": "Unsupported RPC method"
    }